3M™ Cold Shrink QT-III Outdoor Terminations offer easy installation and reliable performance when terminating indoor and outdoor medium voltage cable. The Hi-K stress control design delivers excellent BIL performance and lower surface stress, resulting in a more compact termination. 3M™ Cold Shrink QT-III 7690-S Series Termination Kit includes 3 single-conductor, skirted terminations. It ensures a pliable, tight seal for tape shield, wire shield and UniShield® power cables. The conjunction of high dielectric-constant material and sealing compounds allows the termination to withstand voltages of 5 to 35kV.
The 3M™ QT-III Cold Shrink Inverted Outdoor Termination Kit 7620 S & 7690 S Series uses a conjunction of high dielectric constant material and sealing compounds that allows the termination to withstand voltages of 5 to 35kV.
BIL | 200 kV |
Brands | 3M™ |
Breakout Boot | No |
Cable Insulation Outside Diameter Range | 1.05-1.80 in |
Cable Insulation Outside Diameter Range (metric) | 26.7 - 45.7 mm |
Cable Shielding | UniShield®, Wire Shield, Tape Shield |
Case Quantity | 1 |
Compatible Lug | QL2-A-4/0-600, QL2-A-350-750 |
Conductor Sizes (Imperial) | 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 400 kcmil, 500 kcmil, 600 kcmil, 700 kcmil, 750 kcmil, 800 kcmil, 900 kcmil, 1000 kcmil, 1250 kcmil, 1500 kcmil |
Indoor/Outdoor | Outdoor Skirted Inverted |
Insulation Level | 100%, 133% |
Insulation Outer Diameter (Imperial) | 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in, 1.19 in, 1.2 in, 1.21 in, 1.22 in, 1.23 in, 1.24 in, 1.25 in, 1.26 in, 1.27 in, 1.28 in, 1.29 in, 1.3 in, 1.31 in, 1.32 in, 1.33 in, 1.34 in, 1.35 in, 1.36 in, 1.37 in, 1.38 in, 1.39 in, 1.4 in, 1.41 in, 1.42 in, 1.43 in, 1.44 in, 1.45 in, 1.46 in, 1.47 in, 1.48 in, 1.49 in, 1.5 in, 1.51 in, 1.52 in, 1.53 in, 1.54 in, 1.55 in, 1.56 in, 1.57 in, 1.58 in, 1.59 in, 1.6 in, 1.61 in, 1.62 in, 1.63 in, 1.64 in, 1.65 in, 1.66 in, 1.67 in, 1.68 in, 1.69 in, 1.7 in, 1.71 in, 1.72 in, 1.73 in, 1.74 in, 1.75 in, 1.76 in, 1.77 in, 1.78 in, 1.79 in, 1.8 in |
Insulation Outer Diameter (metric) | 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm, 30.226 mm, 30.48 mm, 30.734 mm, 30.988 mm, 31.242 mm, 31.496 mm, 31.75 mm, 32.004 mm, 32.258 mm, 32.512 mm, 32.766 mm, 33.02 mm, 33.274 mm, 33.528 mm, 33.782 mm, 34.036 mm, 34.29 mm, 34.544 mm, 34.798 mm, 35.052 mm, 35.306 mm, 35.56 mm, 35.814 mm, 36.068 mm, 36.322 mm, 36.576 mm, 36.83 mm, 37.084 mm, 37.338 mm, 37.592 mm, 37.846 mm, 38.1 mm, 38.354 mm, 38.608 mm, 38.862 mm, 39.116 mm, 39.37 mm, 39.624 mm, 39.878 mm, 40.132 mm, 40.386 mm, 40.64 mm, 40.894 mm, 41.148 mm, 41.402 mm, 41.656 mm, 41.91 mm, 42.164 mm, 42.418 mm, 42.672 mm, 42.926 mm, 43.18 mm, 43.434 mm, 43.688 mm, 43.942 mm, 44.196 mm, 44.45 mm, 44.704 mm, 44.958 mm, 45.212 mm, 45.466 mm, 45.72 mm |
Insulation Rejacketing | No |
Lug/Stem Connector Included in Kit | No |
Maximum Installed Length | 16.00 in |
Number of Conductors | 1 |
Number of Skirts | 4 |
Product Series | 7600-S-INV |
Voltage | 5 kV, 8 kV, 15 kV, 25 kV, 35 kV |
Voltage Application | Medium Voltage |