3M™ Rejacketing Sleeves RJS Series are designed so that 3M™ Cold Shrink QT-III and Q-TIII Silicone Rubber Terminations can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armoured and non-armoured configurations. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. The 3M™ Rejacketing Sleeve RJS-5/10 is to be used in conjunction with 3M™ Cold Shrink Breakout Boots and Silicone Rubber Terminations. 3M™ Rejacketing Sleeve RJS-5/10 has a metallic shield diameter range of 1.28-1.62 inch (32.5-41.1 mm), a voltage range of 3.3-35.0 kV, and one 10-foot (3 m) coil per case.
3M™ Rejacketing Sleeves RJS Series are designed so that 3M™ Cold Shrink QT-III & Q-TIII Silicone Rubber Terminations can be used on 3/C (three conductor) medium voltage shielded power cables of tape shield, wire shield, armoured and non-armoured configurations. Rejacketing sleeves are designed to protect the phase legs (core) of 3/C shielded power cable from exposure to moisture, corrosion, ozone, ultra-violet radiation, physical contact and other hazards that are associated with termination operating environments. 3M™ Rejacketing Sleeve RJS-5/10 are designed to be used in conjunction with 3M™ Cold Shrink Breakout Boots and Silicone Rubber Terminations.
Brands | 3M™ |
Breakout Boot | No |
Dielectric Strength (V/mil) | 428 V/mil |
Elongation | 910 % |
Inner Diameter After Shrink (Imperial) | 1.3 in |
Inner Diameter After Shrink (Metric) | 32.5 mm |
Inner Diameter Before Shrink (Imperial) | 1.62 in |
Inner Diameter Before Shrink (Metric) | 41.1 mm |
Insulation Rejacketing | Yes |
Metallic Shield Diameter Range | 1.28 - 1.62 in |
Operating Temperature (Celsius) | 105 |
Operating Temperature (Fahrenheit) | 194 |
Product Colour | Dark Grey |
Product Type | Splice Jacketing and Rejacketing Kits |
Temperature Rating | 356°F (180°C) Class H |
Tensile Strength (Imperial) | 1058 Pound-Force Per Square Inch |
Units per Case | 1.0 |
Voltage Range | 3.3 - 35 kV |
Overall Length (Imperial) | 10 ft |
Overall Length (Metric) | 3048 mm |