1. Canada
  2. All 3M Products
  3. Electrical
  4. Power Cable Connectors
  5. Power Cable Terminations
  6. 3M™ Cold Shrink QT-II Termination Kit 5635K, 3/Kit

3M™ Cold Shrink QT-II Termination Kit 5635K, 3/Kit

  • 3M ID 7000031453

Track-resistant silicone rubber insulators with built-in Hi-K stress relief

Easy installation;insulators are pre-stretched around a spiral-wound, plastic core

Void-free, flexible seal without special tools or torches

View more details
Frequently viewed resources
PDF (1) Copy 26Safety Data Sheet (PDF)

Details

Highlights
  • Track-resistant silicone rubber insulators with built-in Hi-K stress relief
  • Easy installation;insulators are pre-stretched around a spiral-wound, plastic core
  • Void-free, flexible seal without special tools or torches
  • Each kit includes all the materials necessary to make 3 terminations are included (except lugs)
  • Conductor Size Ranges: · 5 kV (100%): 8-2/0 AWG · 5 kV (133%): 8-1/0 AWG · 8 kV (100%): 8-1/0 AWG · 8 kV (133%): 8-1 AWG · 15 kV (100%): 8-4 AWG · 15 kV (133%): 8-6 AWG
  • Withstands voltages of 5 to 15kV and is 110 kV BIL-rated
  • Includes three 4-skirt, 1-piece, cold shrink terminations
  • Meets IEEE Standard 48, Class 1 for outdoor, weather-exposed applications

3M™ Cold Shrink QT-II Termination Kits provide easy installation for a broad spectrum of indoor and outdoor applications. When the terminator is slipped over a properly prepared cable and the core is removed, the terminator immediately shrinks to the cable's dimensions. The result is a void-free, flexible seal without special tools or torches.

Each 3M™ Cold Shrink QT-II Termination Kit includes: Three 3M™ Hi–K Silicone Rubber Terminations, three 3M™ Mechanical Ground Strap Assemblies, three 3M™ Sealing Mastic Strips, one roll of Scotch® 13 Semi-Conducting Tape, one roll of Scotch® 70 Silicone Rubber Tape, three packs of 3M™ Silicone Grease, one Scotch® Cable Preparation Kit and 1 Instruction Sheet.

Suggested applications
  • For terminating tape, wire, and Unishield® shielded cable
  • Lightweight for either free-hanging or bracket-mounting arrangements

Typical Properties

Applications

Cable Termination

BIL

110 kV

Brands

3M™

Breakout Boot

No

Cable Insulation Outside Diameter Range

0.84-1.33 in

Cable Insulation Outside Diameter Range (metric)

21.3-33.8 mm

Cable Shielding

Tape Shield, UniShield®, Wire Shield, Wire-Over-Tape Shield

Case Quantity

1

Conductor Sizes (Imperial)

2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 400 kcmil, 500 kcmil, 600 kcmil, 700 kcmil, 750 kcmil

Indoor/Outdoor

Outdoor Skirted

Insulation Level

100%, 133%

Insulation Outer Diameter (Imperial)

0.84 in, 0.85 in, 0.86 in, 0.87 in, 0.88 in, 0.89 in, 0.9 in, 0.91 in, 0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in, 1.19 in, 1.2 in, 1.21 in, 1.22 in, 1.23 in, 1.24 in, 1.25 in, 1.26 in, 1.27 in, 1.28 in, 1.29 in, 1.3 in, 1.31 in, 1.32 in, 1.33 in

Insulation Outer Diameter (metric)

21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm, 30.226 mm, 30.48 mm, 30.734 mm, 30.988 mm, 31.242 mm, 31.496 mm, 31.75 mm, 32.004 mm, 32.258 mm, 32.512 mm, 32.766 mm, 33.02 mm, 33.274 mm, 33.528 mm, 33.782 mm

Insulation Rejacketing

No

Lug/Stem Connector Included in Kit

No

Maximum Installed Length

12.00 in

Number of Conductors

1

Number of Skirts

4

Product Colour

Grey

Product Series

5630K

Voltage

5 kV, 8 kV, 15 kV

Resources

Safety Data Sheets

Document Number: MSDS_2678472_CA_EN

(PDF)