1. Canada
  2. All 3M Products
  3. Electrical
  4. Splices & Accessories
  5. Cold Shrink Splices
  6. 3M™ Cold Shrink QS-III Splice Kit, 5525A-350-A, shielded armoured and non-armoured cable, 25/28 kV, 1.07 - 1.7 in (27.2 - 43.2 mm) O.D., 250-750 kcmil (120-325 mm²)

3M™ Cold Shrink QS-III Splice Kit, 5525A-350-A, shielded armoured and non-armoured cable, 25/28 kV, 1.07 - 1.7 in (27.2 - 43.2 mm) O.D., 250-750 kcmil (120-325 mm²)

  • 3M ID 7000006185
  • UPC 00054007421382

Quick and easy installation

Silicone body provides excellent electrical performance and excellent low temperature handling

No heat, flames, or special tools required

View more details
Frequently viewed resources
PDF (1) Copy 26Safety Data Sheet (PDF)

Details

Highlights
  • Quick and easy installation
  • Silicone body provides excellent electrical performance and excellent low temperature handling
  • No heat, flames, or special tools required
  • Allows for transitioning of different size cables
  • Rated for 25/28 kV class cables
  • High-voltage, production-tested for partial discharge and AC ensure reliability

3M™ Cold Shrink QS-III Splice Kit 5525A Series is an inline splice designed to join 25/28 kV tape shield, wire shield, UniShield® or longitudinally corrugated shielded power cables. The cold shrink design fits type MV-90/MV-105 cables with copper conductors while ensuring a quick installation and better cable size transitions. The kit is 15,000 amps-rated for faults current protection.

This kit includes one 3M™ Cold Shrink Silicone Rubber Splice Body, one 3M™ Cold Shrink Adapter Tube, one 3M™ Cold Shrink Jacketing Tube, two 3M™ Red Compound Tubes P55/R, six Scotch® Mastic Sealing Strips 2230, two rolls of Scotch® Rubber Mastic Tape 2228, one 3M™ Cable Cleaning Pad CC-3, one cable preparation template, one shielding sleeve, one ground strap, five constant force spring ground connectors, two copper foil tape strips, and an instruction booklet.

Suggested applications
  • Inline splice for joining tape shield, wire shield, UniShield® or longitudinally corrugated shielded power cables
  • Designed for inline splicing, feeder and distribution circuits, size transition splicing, direct burial installations and submerged locations

Typical Properties

Brands

3M™

Cable Shielding

UniShield®, Tape Shield, Wire Shield, Longitudinally Corrugated (LC)

Conductor Material

Copper/Aluminum

Insulation Outer Diameter (Imperial)

0.894 in

Insulation Outer Diameter (metric)

27.2 mm

Maximum Conductor Size (Imperial)

750 kcmil

Maximum Conductor Size (Metric)

400 mm²

Minimum Conductor Size (Imperial)

500 kcmil

Minimum Conductor Size (Metric)

240 mm²

Number of Conductors

1

Voltage

25/28 kV

Resources

Safety Data Sheets

Document Number: MSDS_2645190_CA_EN

(PDF)