  6. 3M™ Cold Shrink QT-III Outdoor 8 Skirt Termination Kit, 7685-S-8, shielded cable, 5-35 kV, 1.05-1.80 in (26.7-45.7 mm) cable insulation O.D., 3 terminations per kit

3M™ Cold Shrink QT-III Outdoor 8 Skirt Termination Kit, 7685-S-8, shielded cable, 5-35 kV, 1.05-1.80 in (26.7-45.7 mm) cable insulation O.D., 3 terminations per kit

  • 3M ID 7000006129
  • UPC 00054007424673

Quick installation with versatile one-piece design

No torches, heat or special tools required

Hi-K stress control

View more details
Frequently viewed resources
PDF (1) Copy 26Safety Data Sheet (PDF)

Details

Highlights
  • Quick installation with versatile one-piece design
  • No torches, heat or special tools required
  • Hi-K stress control
  • Excellent tracking resistance, UV resistance and water-shedding properties
  • Includes everything required to make 3 terminations (except lugs)
  • Conductor size ranges: 5 kV: 700-1500 kcmil 8 kV: 600-1250 kcmil 15 kV: 500-1000 kcmil 25/28 kV: 250-800 kcmil 35 kV: 3/0 AWG-600 kcmil

3M™ Cold Shrink QT-III Outdoor Terminations offer easy installation and reliable performance when terminating indoor and outdoor medium voltage cable. The Hi-K stress control design delivers excellent BIL performance and lower surface stress, resulting in a more compact termination. The 3M™ Cold Shrink QT-III Outdoor 8 Skirt Termination Kit 7685-S-8 has a conductor size range for 5 kV: 700-1500 kcmil, 8 kV: 600-1250 kcmil, 15 kV: 500-1000 kcmil, 25/28 kV: 250-800 kcmil and 35 kV: 3/0 AWG-600 kcmil.

Each kit contains: Three 3M™ Hi–K Tracking Resistant Silicone Rubber Terminations, three 3M™ Preformed Ground Braids, three 3M™ Constant Force Springs, three 3M™ EMI Copper Foil Shielding Tape Strips 1181, six Scotch® Mastic Strips 2230, one 3M™ Cable Cleaning Preparation Kit CC-2, and one Instruction Sheet.

Suggested applications
  • Terminating solid dielectric shielded power cable
  • Tape shield, wire shield and Unishield® constructions
  • Free-hanging or bracket-mounting arrangements
  • Compact design provides for easier installation in restricted spaces
  • Switchgear, transformer, motor lead, bus and similar connections
  • For outdoor use

Typical Properties

BIL

200 kV

Brands

3M™

Breakout Boot

No

Cable Insulation Outside Diameter Range

1.05-1.80 in

Cable Insulation Outside Diameter Range (metric)

26.7 - 45.7 mm

Cable Shielding

Tape Shield, UniShield®, Wire Shield, Jacketed Concentric Neutral (JCN), Longitudinally Corrugated (LC)

Case Quantity

1

Compatible Lug

QL2-A-4/0-600, QL2-A-350-750

Conductor Sizes (Imperial)

3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 400 kcmil, 500 kcmil, 600 kcmil, 700 kcmil, 750 kcmil, 800 kcmil, 900 kcmil, 1000 kcmil, 1250 kcmil, 1500 kcmil

Indoor/Outdoor

Outdoor Skirted

Insulation Level

100%, 133%

Insulation Outer Diameter (Imperial)

1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in, 1.13 in, 1.14 in, 1.15 in, 1.16 in, 1.17 in, 1.18 in, 1.19 in, 1.2 in, 1.21 in, 1.22 in, 1.23 in, 1.24 in, 1.25 in, 1.26 in, 1.27 in, 1.28 in, 1.29 in, 1.3 in, 1.31 in, 1.32 in, 1.33 in, 1.34 in, 1.35 in, 1.36 in, 1.37 in, 1.38 in, 1.39 in, 1.4 in, 1.41 in, 1.42 in, 1.43 in, 1.44 in, 1.45 in, 1.46 in, 1.47 in, 1.48 in, 1.49 in, 1.5 in, 1.51 in, 1.52 in, 1.53 in, 1.54 in, 1.55 in, 1.56 in, 1.57 in, 1.58 in, 1.59 in, 1.6 in, 1.61 in, 1.62 in, 1.63 in, 1.64 in, 1.65 in, 1.66 in, 1.67 in, 1.68 in, 1.69 in, 1.7 in, 1.71 in, 1.72 in, 1.73 in, 1.74 in, 1.75 in, 1.76 in, 1.77 in, 1.78 in, 1.79 in, 1.8 in

Insulation Outer Diameter (metric)

26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm, 28.702 mm, 28.956 mm, 29.21 mm, 29.464 mm, 29.718 mm, 29.972 mm, 30.226 mm, 30.48 mm, 30.734 mm, 30.988 mm, 31.242 mm, 31.496 mm, 31.75 mm, 32.004 mm, 32.258 mm, 32.512 mm, 32.766 mm, 33.02 mm, 33.274 mm, 33.528 mm, 33.782 mm, 34.036 mm, 34.29 mm, 34.544 mm, 34.798 mm, 35.052 mm, 35.306 mm, 35.56 mm, 35.814 mm, 36.068 mm, 36.322 mm, 36.576 mm, 36.83 mm, 37.084 mm, 37.338 mm, 37.592 mm, 37.846 mm, 38.1 mm, 38.354 mm, 38.608 mm, 38.862 mm, 39.116 mm, 39.37 mm, 39.624 mm, 39.878 mm, 40.132 mm, 40.386 mm, 40.64 mm, 40.894 mm, 41.148 mm, 41.402 mm, 41.656 mm, 41.91 mm, 42.164 mm, 42.418 mm, 42.672 mm, 42.926 mm, 43.18 mm, 43.434 mm, 43.688 mm, 43.942 mm, 44.196 mm, 44.45 mm, 44.704 mm, 44.958 mm, 45.212 mm, 45.466 mm, 45.72 mm

Insulation Rejacketing

No

Lug/Stem Connector Included in Kit

No

Maximum Installed Length

20.50 in

Number of Conductors

1

Number of Skirts

8

Product Series

7680-S

Units per Case

3.0

Voltage

5 kV, 8 kV, 15 kV, 25 kV, 35 kV

Voltage Application

Medium Voltage