The 3M™ QT-II Cold Shrink Outdoor Termination Kit 5601 includes a 4 skirt, 1 piece termination. It ensures a pliable, tight seal for concentric neutral cables. The conjunction of high dielectric constant material and silicone rubber insulation allows the termination to withstand voltages of 5 to 15kV.
The 3M™ QT-II Cold Shrink Outdoor Termination Kit 5601 consists of a high dielectric constant (Hi-K) stress control tube insulated with a moulded silicone skirted insulator. There is a four-skirt design rated 15 kV, six-skirt design rated 25/28 kV, and an eight-skirt design rated 35kV. They are provided in an expanded state, mounted on a removable inner supporting plastic core.
Applications | Cable Termination |
BIL | 110 kV |
Brands | 3M™ |
Breakout Boot | No |
Cable Insulation Outside Diameter Range | 0.64 to 1.12 in |
Cable Insulation Outside Diameter Range (metric) | 16.3 to 28.4 mm |
Cable Shielding | Concentric Neutral (CN) |
Case Quantity | 1 |
Conductor Sizes (Imperial) | 1 AWG, 2 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG, 250 kcmil, 300 kcmil, 350 kcmil, 400 kcmil, 500 kcmil |
Indoor/Outdoor | Outdoor Skirted |
Insulation Level | 100%, 133% |
Insulation Outer Diameter (Imperial) | 0.64 in, 0.65 in, 0.66 in, 0.67 in, 0.68 in, 0.69 in, 0.7 in, 0.71 in, 0.72 in, 0.73 in, 0.74 in, 0.75 in, 0.76 in, 0.77 in, 0.78 in, 0.79 in, 0.8 in, 0.81 in, 0.82 in, 0.83 in, 0.84 in, 0.85 in, 0.86 in, 0.87 in, 0.88 in, 0.89 in, 0.9 in, 0.91 in, 0.92 in, 0.93 in, 0.94 in, 0.95 in, 0.96 in, 0.97 in, 0.98 in, 0.99 in, 1 in, 1.01 in, 1.02 in, 1.03 in, 1.04 in, 1.05 in, 1.06 in, 1.07 in, 1.08 in, 1.09 in, 1.1 in, 1.11 in, 1.12 in |
Insulation Outer Diameter (metric) | 16.256 mm, 16.51 mm, 16.764 mm, 17.018 mm, 17.272 mm, 17.526 mm, 17.78 mm, 18.034 mm, 18.288 mm, 18.542 mm, 18.796 mm, 19.05 mm, 19.304 mm, 19.558 mm, 19.812 mm, 20.066 mm, 20.32 mm, 20.574 mm, 20.828 mm, 21.082 mm, 21.336 mm, 21.59 mm, 21.844 mm, 22.098 mm, 22.352 mm, 22.606 mm, 22.86 mm, 23.114 mm, 23.368 mm, 23.622 mm, 23.876 mm, 24.13 mm, 24.384 mm, 24.638 mm, 24.892 mm, 25.146 mm, 25.4 mm, 25.654 mm, 25.908 mm, 26.162 mm, 26.416 mm, 26.67 mm, 26.924 mm, 27.178 mm, 27.432 mm, 27.686 mm, 27.94 mm, 28.194 mm, 28.448 mm |
Insulation Rejacketing | No |
Lug/Stem Connector Included in Kit | No |
Maximum Installed Length | 8.50 in |
Number of Conductors | 1 |
Number of Skirts | 4 |
Product Series | 5600 |
Voltage | 5 kV, 8 kV, 15 kV |
Safety Data Sheets
Document Number: MSDS_2632537_CA_EN
(PDF)